Search Results

Now showing 1 - 1 of 1
  • PublicationOpen Access
    Selective harmonic mitigation: limitations of classical control strategies and benefits of model predictive control
    (IEEE, 2023) Rosado Galparsoro, Leyre; Samanes Pascual, Javier; Gubía Villabona, Eugenio; López Taberna, Jesús; Ingeniería Eléctrica, Electrónica y de Comunicación; Institute of Smart Cities - ISC; Ingeniaritza Elektrikoa, Elektronikoaren eta Telekomunikazio Ingeniaritzaren; Universidad Pública de Navarra / Nafarroako Unibertsitate Publikoa
    Selective harmonic mitigation pulsewidth modulation (SHMPWM) combined with model predictive control (MPC) is a promising approach for grid-connected power converters. SHMPWM can guarantee grid code compliance in steady state, e.g. grid harmonic injection, with a reduced output converter filter, while MPC improves dynamic response and allows grid code compliance in the event of grid transients. This paper presents a survey of the MPC strategies already published in the literature developed for their use with SHMPWM. The existing strategies fall into two categories: direct model predictive control with an implicit selective harmonic mitigation modulator, and direct model predictive control based on finite control set (FCS-MPC). One representative control strategy of each group is compared to each other and to the performance of classical proportional- integral (PI) controllers combined with SHMPWM. The goal is to identify the potential benefits of MPC for grid-connected power converters, and determine the main advantages and limitations of the two selected state-of-the-art control strategies. Their performance is assessed through Hardware-in-the-Loop (HIL) experimental results in terms of real-time implementation, harmonic content grid code compliance, dynamic response and performance under grid transients.