Energy assessment of waste water heat exchanger and solar energy panel connected to district heating

View/ Open
Date
2013Author
Version
Acceso abierto / Sarbide irekia
Type
Proyecto Fin de Carrera / Ikasketen Amaierako Proiektua
Impact
|
nodoi-noplumx
|
Abstract
This project has the aim of calculating the efficiency of the tap water system, in explicit the
heating of tap water, in Furugården, Valbo. Furugården is a new retirement home, building
Furugården finished in 2013. The building is equipped with a waste water heat exchanger,
solar collectors and in addition to that district heating.
The temperature of hot water has to be above 55°C to minimize ...
[++]
This project has the aim of calculating the efficiency of the tap water system, in explicit the
heating of tap water, in Furugården, Valbo. Furugården is a new retirement home, building
Furugården finished in 2013. The building is equipped with a waste water heat exchanger,
solar collectors and in addition to that district heating.
The temperature of hot water has to be above 55°C to minimize the change of legionella to
develop in the system. The process of heating a building and tap water is a high energy using
process. An aspect what also has to be taken in account is the environment. The waste water
and solar collectors can be seen as sustainable efficient systems. These systems should lower
the output of pollutions and lower the costs of heating tap water.
The waste water system increases the temperature of fresh cold water from an average
temperature of 12°Celcius to 20°Celcius. This results in a increasing of 8°Celcius. From this
result we can conclude that the system will save energy and costs.
It would be an improvement install sensors of temperatures inside the incoming and outgoing
pipes of the waste water system in order to know the efficiency of that
Regarding the efficiency of solar collector heat exchanger, the results obtained has been
successfully as theoretically expected. It is around 95% of the heat transfer from the solar
collector is absorbs for the water flow on the second circuit of such system.
The efficiency of the water tanks are not always working. This is because of a too high
temperature in the collector system. When the temperature is too high, the pumps are not
working and the system stops. This problem can be solved when the system has the right
adjustments. [--]
Subject
Intercambiadores de calor de aguas residuales,
Colectores solares,
Calefacción urbana,
Valoración energética,
Eficiencia energética,
Waste water heat exchangers,
Solar collectors,
District heating,
Energy assessment,
Energy efficiency
Departament
Universidad Pública de Navarra. Departamento de Ingeniería Eléctrica y Electrónica /
Nafarroako Unibertsitate Publikoa. Ingeniaritza Elektrikoa eta Elektronikoa Saila
Degree
Ingeniería Técnica Industrial /
Industria Ingeniaritza Teknikoa