Abstract
Parallel interleaved converters for high power renewable energy systems present stability issues at the LCL resonance frequency. A multisampled measurement and filtering strategy is proposed to stabilize the system based on the capacitor voltage derivative active damping, overcoming its limitations for low switching power converters. The effects of the delays on the stability of the active damping strategy would be analysed. The solution developed is robust against grid inductance variations, ensuring the fulfilment of the stringent harmonic grid codes.
Description
Keywords
Department
Faculty/School
Degree
Doctorate program
item.page.cita
item.page.rights
© 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other work
Los documentos de Academica-e están protegidos por derechos de autor con todos los derechos reservados, a no ser que se indique lo contrario.